Inverter leakage problem analysis

Jan 06, 2025 Leave a message

Some sites use inverter control motor will appear leakage problems, leakage voltage of tens of volts to 200 volts, here for the cause of this failure to analyze the theory. We all know that the motor's three-phase stator windings flow through the current generating a rotating magnetic field, according to the principle of magnetic induction, the motor casing will produce induced electromotive force, the size of this electromotive force depends on the size of the switching frequency of the frequency converter IGBT, due to the high-performance control requirements of high switching frequency, the switching speed is very fast, then the DV/DT is large, at the same time, this induced electromotive force is large, the person touches on the There is a feeling of electric shock. Theoretically, the faster the switching speed of the IGBT, the higher the induced electromotive force on the motor shell, and the higher the control accuracy and response of the inverter to the motor, the higher the feeling of being electrified after touching, on the contrary, the switching frequency of the IGBT is slow, the induced electromotive force will be small, and the feeling of touching will be small, so the domestic low-end inverter design of the switching frequency is on the low side, and the induced electromotive force after controlling the motor is small, and people touching it don't have any feeling. But its control is poor, the dynamic response is slow.

 

info-1-1

 

The output of inverter is controlled by PWM (Pulse Width Modulation, similar to high speed switching), therefore, high frequency leakage current will occur. The following factors can determine the size of the leakage current of the system, and select the appropriate leakage circuit breaker and the necessary measures to improve the phenomenon of leakage circuit breaker tripping after power supply. First of all, inverter, front power supply transformer, motor three transmission equipment PE point must be connected together, and then unified to ground.


Frequency converter is a high-frequency square wave voltage output, due to the existence of equivalent capacitance between the motor internal coil and the motor shell, thus generating leakage current. If not grounded or poorly grounded, there will be leakage phenomenon.


Factors affecting the size of the leakage current are:


(1) Leakage current of the cable line (there are two parts)

Leakage current of the cable length of leakage circuit breaker and filter. Leakage current of the cable length of inverter and motor.

(2) Leakage current of filter (including inverter).

(3) Leakage current of motor.


Some sites use inverter to control the motor, there will be leakage problems, leakage voltage of a few dozen volts to 200 volts ranging from voltage. For this problem, the reasons for this phenomenon are analyzed as follows:

 

According to the functional block diagram of the inverter controlling motor operation, the three-phase power supply is rectified by the rectifier bridge of the inverter, and then sent to the inverter bridge (IGBT) through capacitor filtering, and then the inverter bridge outputs three-phase alternating current with adjustable frequency and voltage to control the operation of the motor.


The three-phase alternating current with a 120 degree difference flows through the three-phase stator coil winding of the motor, generating a rotating magnetic field, so that the rotor of the motor rotates automatically under the action of the rotating magnetic field of the stator winding.


The three-phase stator winding of the motor produces a rotating magnetic field after the current flows through it, and according to the principle of electromagnetic induction, an induced electromotive force (EMF) is generated in the motor casing. The size of this induced electromotive force depends on the size of the switching frequency of the inverter IGBT and C×DV/DT (related to the switching speed of the IGBT). If this induced electromotive force is large, then the human touch will feel like an electric shock. Theoretically, the higher the switching frequency of the IGBT, the motor shell of the effective value of the induced electromotive force (i.e., induced voltage) is higher, and the frequency converter on the motor control accuracy and dynamic response is also higher, the human body touched after the feeling of being electrified is greater; Conversely, the lower the switching frequency of the IGBT, the motor shell of the effective value of the induced electromotive force (induced voltage) is lower, and from the body after the touch of being electrified is the feeling of being smaller. Smaller.


Due to the asynchronous motor operation, the motor shell will have induced voltage (the so-called leakage), so the motor manufacturer will be in the motor factory, in the junction box inside the grounding terminal, to facilitate the user in the application of connecting to the earth in order to eliminate the induced electromotive force (i.e., to eliminate the induced leakage voltage), in order to solve the human body when touching the motor to be the feeling of electricity.


When the motor is operated by industrial frequency, the switching frequency of industrial frequency is about 50HZ, which is very low, so there is almost no feeling of leakage in general (unless the insulation of the motor is very poor). While inverter control, because of its switching frequency are much higher than the frequency of the industrial frequency, so the inverter in the control of motor rotation, the motor shell will have the feeling of leakage.