With the continuous advancement of industrial automation, variable frequency air compressors have gradually become mainstream products in the market, and variable frequency drives (VFDs) have also gained extensive application. The VFD in variable frequency air compressors adjusts the output voltage and frequency by switching its internal IGBTs, providing the motor with the required power voltage based on its actual needs to achieve energy savings and speed regulation. However, the hazards brought about by the widespread use of VFDs should not be overlooked. In the motor field, VFDs may potentially damage motors and disrupt normal operating conditions to some extent.
While the energy-saving retrofits achieved by VFDs in variable-frequency air compressors are significant, the issue of harmonic pollution from these drives has become increasingly severe. Different enterprises encounter varying challenges during VFD implementation. In summary, harmonics primarily cause damage to certain equipment, necessitating the installation of filtering devices like reactors to mitigate the problem-which also presents opportunities for copper applications. Below, we detail which equipment is susceptible to harmonic damage.
What harm can inverter harmonics cause?
1. Transformers
Current harmonics increase copper losses, while voltage harmonics increase iron losses. The combined effect raises transformer temperatures, compromising insulation integrity and reducing capacity margin. Harmonics may also induce resonance between transformer windings and inter-wire capacitance, or cause core magnetic saturation/distortion, generating noise.
2. Electric Motors
Harmonic output primarily affects motors by inducing additional heating, leading to elevated temperature rises. Motors often require derating. Distorted output waveforms increase repetitive peak voltages, compromising motor insulation. Harmonics also cause torque pulsations and heightened noise levels.
3. Switchgear
Harmonic currents induce extremely high di/dt current rates during switchgear startup, elevating transient recovery voltage peaks and potentially compromising insulation integrity.
4. Power Capacitor Banks
Standard specifications limit capacitor overload to 35% of rated current. However, harmonic effects frequently cause severe overloads during operation. As capacitor impedance decreases with increasing frequency, harmonics cause capacitors to act as current traps, drawing excessive currents. This leads to overheating, increased dielectric stress, and potential damage. When capacitor and line impedances resonate, vibration-induced short circuits, overcurrent, and noise generation occur.
5. Metering Instruments
Metering instruments like electric energy meters experience additional electromagnetic torque on their induction rotors due to harmonics, causing measurement errors and reduced accuracy.
6. Protective Devices
Harmonics in the current generate extra torque, altering the operational characteristics of protective devices and potentially causing false tripping.
Other equipment such as lighting systems, communication devices, computer equipment, and carrier-frequency remote control systems are also susceptible to harmonic interference, which can disrupt normal operation or shorten service life.
7. Power Electronic Equipment
In various applications, electronic devices often serve as harmonic current sources and are highly sensitive to harmonic distortion, leading to malfunctions.